The problem with using 2-way Chilled Water control valves.
As a system with two-way control valves becomes
satisfied, it begins to close its two-way valve. The greater the number of two way valves
closed, the greater the head against the chilled water flow to the building and
the greater the head against the chilled water pumps.
In a two-way installation, the temperature difference
between chilled water supply and chilled water return is not an adequate
indication of the building's load.
Since the overall building chilled water flow
decreases as the load decreases, the temperature difference does not always
change, especially if there are leaky bypass differential valves. Water flow downstream of the bypass
differential valves is the beat indication of true building load.
In situations where many similar zones are drawing
from a common supply, the problem of selecting the highest multitude of the
valve positions may be circumvented.
Determining the highest multitude of valve positions is the best way to
control the entire system.
If all the valves are the two-way type, flow will vary
directly with heat load under conditions of constant supply temperature.
A valve position control system would attempt to
maximize the valve positions, and therefore flow, by raising supply temperature
to its highest acceptable level.
A flow controller setting supply temperature can reach
the same objective. As the terminal units
reduce their individual flow rates due to a decrease in cooling load, the flow
controller will respond by gradually raising the overall supply
temperature.
In the steady state condition, total flow will have to
be restored, with the decrease in cooling
load being reflected by a temperature change, rather than the expected flow
change. Like a valve position
controller, this flow controller requires integral action with a time constant long enough for the zones to respond.
There is never a guarantee that controlling the total
flow will satisfy all the zones. It is
actually only capable of satisfying the average zone. Reducing the flow set point somewhat below
the maximum attainable value can provide some measure of protection.
This might be acceptable for most air-conditioning
systems where cooling loads are generally evenly distributed and being affected
by similarly ambient conditions and occupancy.
In cases where one or two critical zones may
periodically require more cooling than the average, a valve position controller
can be utilized to operate those particular zones. The valve position controller could then
override the flow controller to insure the selected critical zone is satisfied. During the override situation, total flow
would fall below its set point as the other zones reduce their demand for
cooling.
In order for the building's two-way valves to
inter-relate properly with the control system and any building interface, it is
advisable for the two-way valves to be the equal percentage type, selected on
an adequate pressure differential.
In general, equal percentage valves selected in such a
way that their overall pressure drop is 10% of the circuit pressure drop,
provides efficient control.
Learn more
Labels: chilled water control. HVAC zone control, condenser water control, Control valves, Hal Finkelstein, HVAC building zone control, HVAC control valves, pump control, water pump control
<< Home